From: johnh@macadam.mpce.mq.edu.au (John Haddy) Newsgroups: sci.electronics Subject: Electrical Safety Date: 2 Mar 1994 06:20:49 GMT Organization: Macquarie University, Sydney Australia NNTP-Posting-Host: macadam.mpce.mq.edu.au I wrote the following in response to a thread of a thread with the topic Jacob's Ladders. However, since I feel that the information should reach a wider audience, so I've reposted it with a new topic.
===============
It always amazes me how long it will take before somebody presents attributable data for questions on sci.electronics. What's more shocking (sorry!) is the amount of suspect "I think ..." responses I've seen to such an important field as electrical safety.
From Australian Standard AS3859-1991, based on IEC479-1(1984) and IEC479-2 (1987) "Effects of current passing through the human body":
Table 1:
Values for the total body impedance (ohms) that are not exceeded for a percentage (percentile rank) of Touch Voltage 5% 50% 95% (V) of the population 25 1750 3250 6100 50 1450 2625 4375 75 1250 2200 3500 100 1200 1875 3200 125 1125 1625 2875 220 1000 1350 2125 700 750 1100 1550 1000 700 1050 1500 Asymptotic value 650 750 850
"The values of the total body impedance given in Table 1 are valid for living human beings and a current path hand to hand or hand to foot for large contact areas (50cm^2 to 100cm^2) and dry conditions.
"At voltages up to 50V, values measured with contact areas wetted with normal water are 10% to 25% lower than in dry conditions and conductive solutions decrease the impedance considerably down to half the values measured in dry conditions.
"At voltages higher than approximately 150V the total body impedance depends only slightly on humidity and on the surface area of contact."
From the same document:
This table references Figure 5 of this document, "Time/current zones of effects of a.c. currents (15Hz to 100Hz) on persons.", which I cannot draw due to the nature of the curvy lines, etc.
In summary, Zone 1 lies in the region less than 0.5mA body current, for all durations. Zone 2 extends to about 500mA at 20ms or less duration, to 20mA at 1000ms duration and to 10mA at 10000ms duration. Zone 3 (to curve c2 mentioned) extends from the Zone 2 boundary to 1000mA for 10ms duration, 200mA for 500ms duration and 50mA for 10000ms duration.
I really do recommend that _anybody_ playing with mains powered circuits should get hold of a copy of their country's standard and read it.
JohnH
---------------------------------------------------------------------------- | _ |_ _ |_| _ _| _| Electronics Department |_| (_) | | | | | | (_| (_| (_| \/ School of MPCE ---------------------------------/- Macquarie University Sydney, AUSTRALIA 2109 Email: johnh@mpce.mq.edu.au, Ph: +61 2 805 9090, Fax: +61 2 805 9128 ----------------------------------------------------------------------------